1Installation, Operation and Maintenance ManualforThermal Air Flow Measurement TransmitterVersion 1.4X & 1.5X®

Página 2 - TABLE OF CONTENTS

105.5 – PUSHBUTTON DEFINITIONThe four pushbuttons used to interface with the Vari-Green are as follows: UP DN ENT ESCIn addition to use duri

Página 3 - Phone: 1-800-717-6540

11Main Menu Selection DescriptionOperator Password Selection Allows for the selection of password for the Operator Menu, and the bypassing of the pass

Página 4 - 1 – GENERAL INFORMATION

12 Note: All selections that are available for further configuration programming will have an “arrow” symbol displayed in the right side of the displ

Página 5 - 3 – FEATURES

135.8 – FLOW CONFIGURATIONThis Operator Menu selection is where all application specific data is entered to configure the Vari-Green for a unique applic

Página 6 - 4 – INSTALLATION

14Units List for VolumeUnit of Measurement DisplayActual cubic feet per minute ACFMActual cubic feet per hour ACFHActual liters per second Al/sActual

Página 7 - 4.4 – PROCESS CONNECTIONS

155.9 – DISPLAY CONFIGURATION (con’t)1. While in Operator Menu, use UP or DN to scroll to:2. Press ENT to enter Display Configuration menu. Display wil

Página 8

165.10 – Output 2 Parameter SelectionAllows the selection of which process variables Output 2 represents.Process variables available for output are:

Página 9 - 5 – OPERATION

175.11 – Low Pass FilterAllows selection of level of Process filtering applied to the output. Levels are 0 to 10, with 0 representing no filtering and

Página 10 - 5.5 – PUSHBUTTON DEFINITION

185.13 – Transmitter Output CalibrationAllows for the calibration of the Vari-Green analog outputs.Note: Unit is supplied Factory calibrated.This sect

Página 11

19Pushbutton Combination4-20mAOutput Type 0-5VDC0-10VDCUP only +0.001mA +0.3mV +0.6mVDN only -0.001mA -0.3mV -0.6mVUP* + ESC +0.01mA +0.003V +0.006VDN

Página 12 - - Return to MAIN MENU

2TABLE OF CONTENTSSECTION 1 – GENERAL INFORMATION1.1 DESCRIPTION ...

Página 13 - 5.8 – FLOW CONFIGURATION

205.14 – K-Factor ConfigurationCautionIn the majority of applications, the use of a K-Factor is neither required nor desirable. Before using the K-Fact

Página 14 - 5.9 – DISPLAY CONFIGURATION

215.14 – K-Factor Configuration (con’t)1. While in Operator Menu, use UP or DN to scroll to:2. Press ENT to enter K-Factor Configuration menu. Display w

Página 15

221. While in Main Menu, use UP or DN to scroll to:2. Press ENT to enter Network Configuration menu. Display will indicate:3. Press ENT and display wi

Página 16 - TEMPERATURE

231. While in Main Menu, use UP or DN to scroll to:2. Press ENT to enter Alarm Configuration menu. Display will indicate:3. Press ENT and display will

Página 17 - 5.11 – Low Pass Filter

24Flow Alarm ConfigurationAlarm 1 Off/On SelectionOperator MenuAlarm 1 Off/OnOFFAlarm 2 Off/OnOFFAlarm 1, Low Setpt250 [units]Alarm 2, High Setpt250 [u

Página 18 - Output Calibration Menu

256 - Supervisor Menu6.1 – IntroductionThe Supervisor menu allows individual sensors to be enabled or disabled, scan all sensors for status, and perfo

Página 19

261. While in Supervisor Menu, use UP or DN to scroll to:2. Press ENT to enter Supervisor password menu. Display will indicate:3. Press ENT and disp

Página 20 - 5.14 – K-Factor Configuration

271. While in Operator Menu, use UP or DN to scroll to:2. Press ENT to enter Sensor Management menu. Display will indicate:3. Press ENT to enter Senso

Página 21 - 2 Minutes

289. Press ENT. Display will indicate:This display will indicate which sensors are enabled.Only enabled sensors will be indicated on bar graphn by dar

Página 22 - Network Configuration Menu

296.4 – Diagnostic Display SelectionDiagnostic DisplaySensor Number: 1VELO XXX SFPMTEMP XX.X°F1 to 321- Sensor ManagementDiagnosti

Página 23 - Flow Alarm Configuration Menu

3TABLE OF CONTENTSSECTION 6 – SUPERVISOR MENU 6.1 INTRODUCTION ...

Página 24 - Temp Alarm Configuration Menu

30 4. Use UP or DN to scroll through all sensors that have an alert.Note: Only sensors with an existing alert will be displayed with its alert code.

Página 25 - 6 - Supervisor Menu

316.6 – Power Cycle Sensor NetworkPower CycleAre you sure?NOYES or NO- Diagnostic ALERT DeterminationPower Cycle Sensor Network- SUPERVISOR MENU EXTSu

Página 26 - - Sensor Management

32Personnel should be familar with the operation of the Vari-green (see Section 5) before performing any troubleshooting.Problem SolutionDispaly blank

Página 27 - 6.3 – Sensor Management

33Appendix ABACnet Standardized Device Profile (Annex L)BACnet Operator Workstation (B-OWS)BACnet Building Controller (B-BC)BACnet Advanced Application

Página 28

34X Property Description set by AMC FirmwareX Device_Name set via Vari-Green transmitter menuX Max_Master set via Vari-Green transmitter menuX Max_Inf

Página 29 - Diagnostic Display

35Data Link Layer Options (check all that are supported)BACnet IP, (Annex J)BACnet IP, (Annex J), Foreign DeviceISO 8802-3, Ethernet (Clause 7)ANSI/AT

Página 30

4The Vari-Green utilizes thermal dispersion technology to measure airflow. As air moves across the surface of an elevated temperature sensor, heat is t

Página 31 - 7 - Maintenance

52.1 – ACCURACYSensor Accuracy. Velocity: ±2% of Reading Temperature: ±0.1ºFOverall System Accuracy. Flow: ±2-3% of Actual Flow Temperature: ±0

Página 32 - 8 - Troubleshooting

64 – INSTALLATION4.1 – RECEIVING AND INSPECTION• Carefully remove the Vari-Green Probe(s) or Station, and Transmitter from the shipping container and

Página 33 - Analog Input Object Type

74.4 – PROCESS CONNECTIONSSee separate Installation Instructions provided with the Vari-Green Probes or Station for information on connecting cables f

Página 34 - Device Object Type

84.5 – POWER/SIGNAL CONNECTIONS (con’t)OUTPUT #2 (Terminals 3(+) and 4(-), P7). This output can represent the measured flow (0 - Design Full Range) or

Página 35

9After 20 seconds, the display will return to Normal display mode, and the dot in the upper right of the display indicating CPU Activated will blink r