SERIES 44 INSTALLATION INSTRUCTIONSand field service checklistBULLETIN MI2047-06/04REPLACED MI1079System ComponentsPage 2 Introduction and DimensionsP
2Introduction and DimensionsA discharge air temperature sensor (and mixing tube) is ameans of limiting the minimum and maximum discharge airtemperatur
3Modulator (M) or Modulator-Regulator (MR) Valve: Mount in upright position in horizontal run of pipe, downstream ofother controls - a separate gas p
418. If readings are incorrect, replace the TS144 or repair wiring.1. Install properly.16. Clean, replace valve and/or seat if necessary.17. Clean, or
5Valve Adjustments(See bulletin MT2035 for additional M/MR valve information)NOTE: Low fire adjustment should be checked whenever the high fire adjust
6MT1-12/TS14410K TESTPOTJUMPERVALVE24V20VATRANS.RESISTOR2K10K TEST POTVALVE14V20VATRANS.RESISTOR2KJUMPERPreliminary Circuit Analysis(Terminal location
Note: All electronic components are pre-calibrated to a baseresistance. This permits field replacement without upsettingsystem calibration.Minimum Dis