Modular Small Cabinet Fan 1
®
®
Document 462888
Model MSCF
Modular Small Cabinet Fan
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with instructions could result in personal injury and/or property damage!
Only qualified personnel should install this unit.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards.
Other considerations may be required if high winds
or seismic activity are present. If more information
is needed, contact a licensed professional engineer
before moving forward.
1. Follow all local electrical and safety codes, as
well as the National Electrical Code (NEC), the
National Fire Protection Agency (NFPA), where
applicable. Follow the Canadian Electric Code
(CEC) in Canada.
2. The rotation of the wheel is critical. It must be
free to rotate without striking or rubbing any
stationary objects.
3. Motor must be securely and adequately
grounded.
4. Do not spin fan wheel faster than the maximum
cataloged fan rpm. Adjustments to fan speed
significantly affects motor load. If the fan RPM is
changed, the motor current should be checked
to make sure it is not exceeding the motor
nameplate amps.
DANGER
Always disconnect power before working on or
near a unit. Lock and tag the disconnect switch or
breaker to prevent accidental power up.
CAUTION
When servicing the unit, motor may be hot enough
to cause pain or injury. Allow motor to cool before
servicing.
General Safety Information
5. Do not allow the power cable to kink or come
in contact with oil, grease, hot surfaces,
or chemicals. Replace cord immediately if
damaged.
6. Verify that the power source is compatible with
the equipment.
7. Never open blower access doors while the fan is
running.
Model MSCF-FC
Model MSCF-BI
Vista de página 0
1 2 3 4 5 6 ... 19 20

Resumo do Conteúdo

Página 1 - Model MSCF-BI

Modular Small Cabinet Fan 1®®Document 462888Model MSCFModular Small Cabinet FanInstallation, Operation and Maintenance ManualPlease read and save thes

Página 2 - 2 Modular Small Cabinet Fan

10 Modular Small Cabinet Fan®any two supply power connections will reverse the direction of rotation. To reverse the rotation, turn the power off and

Página 3 - Unit Layout

11Modular Small Cabinet Fan®Symptom Possible Cause Corrective ActionBlower fails to operateBlown fuse or open circuit breaker Replace fuse or reset ci

Página 4 - External Mounting Isolation

12 Modular Small Cabinet Fan®Hot Water and Chilled Water1. Piping should be in accordance with accepted industry standards. Pipework should be suppor

Página 5 - MSCF Mounting Dimensions

13Modular Small Cabinet Fan®2P = minimum2P = minimumDrain Pan / Drain TrapDrain Pan / Drain TrapDrain lines and traps should be run full size from the

Página 6 - Filter Sizes and Quantity

14 Modular Small Cabinet Fan®Installation of Electric Heater (optional)WARNINGElectrical Shock Hazard! Disconnect all power sources before doing any w

Página 7 - Coil Dimensions

15Modular Small Cabinet Fan®Sequence of Operation - Electric Heater1. Electric heaters are divided in to equally sized steps. For example, a 60 kW he

Página 8 - Coil Dimensions - continued

16 Modular Small Cabinet Fan®Every Three (3) MonthsFilters - The filter in the unit should be inspected at least every three (3) months. Depending on t

Página 9

17Modular Small Cabinet Fan®Coil Maintenance Start-Up DocumentationCAUTIONFin edges are sharp.Coils must be clean to obtain maximum performance. Check

Página 10 - System Start-Up

18 Modular Small Cabinet Fan®Optional Ladder Diagrams208V/230V/380V/460V/575V3PH/50Hz/60HzDS1L1XRTR1X24 VACUNIT CONTROL40 VAGRST1A1A2NEUTRAL LINEMOTSU

Página 11 - Troubleshooting

19Modular Small Cabinet Fan®Maintenance LogDate __________________ Time _____________ AM/PMNotes:_____________________________________________________

Página 12 - Start-Up of Coil Module

2 Modular Small Cabinet Fan®The unit should be stored at least 3½ in. (89 mm) off the floor on wooden blocks covered with moisture proof paper or polye

Página 13 - Drain Pan / Drain Trap

462888 • MSCF, Rev. 3, March 2015 Copyright 2015 © Greenheck Fan Corporation20As a result of our commitment to continuous improvement, Greenheck rese

Página 14 - (optional)

3Modular Small Cabinet Fan®Table of ContentsInstallationUnit Layout ...3Mounting / Hanging Instructions ... 4Mo

Página 15 - 15Modular Small Cabinet Fan

4 Modular Small Cabinet Fan®Hanging BracketPart No. 710774Drawing No. 85537Hanging BracketPart No. 710774Drawing No. 85537Bridge BracketPart No. 71177

Página 16 - Fan Maintenance

5Modular Small Cabinet Fan®24 PLENUM12 PLENUMCHILLED WATER COILHEATING COILVERTICALFILTERFANMIXING BOXw/DAMPERMSCF Mounting DimensionsAB C D EFGHMModu

Página 17 - Drain Pan Maintenance

6 Modular Small Cabinet Fan®Dimensional DataFilter Sizes and QuantityUnit SizeA B C DE F GUnit WidthInlet Outletw/o Filterw/ Filter12 in. 24 in. Verti

Página 18 - Optional Ladder Diagrams

7Modular Small Cabinet Fan®Coil DimensionsNOTEFluid enters the coil from the bottom connection (Inlet) and exits from the top (Outlet).Hot Water • 1 a

Página 19 - Maintenance Log

8 Modular Small Cabinet Fan®NOTEWith airflow from left to right, the fluid enters the coil from the bottom connection (Inlet) and exits from the top (

Página 20 - Our Commitment

9Modular Small Cabinet Fan®Direct Expansion (DXI) • 4, 6 or 8 RowDual Circuit with 50/50 Face Interlaced ConstructionNOTEThe first suction header on t

Comentários a estes Manuais

Sem comentários